Specification parameters | |||
project | content | ||
power supply | DC24V, working range (DC 9-30V), anti surge, overcurrent, and reverse connection protection | ||
power | ≤4W | ||
work environment | -25°C ~ +75°C 10~90%RH(No condensation) | ||
CPU | A7 dual core, main frequency 1GHz | ||
Memory | 64M DDR2, 128M Flash | ||
4G frequency band | LTE-FDD: B1/B3/B5/B8 LTE-TDD: B34/B38/B39/B40/B41 GSM: 900/1800 MHz | ||
WIFI standard | 802.11 b/g/n 2.412GHz~2.484GHz | ||
interface type | |||
interface | RS485 | It has electrical isolation and can be used for communication with the lower computer. The wiring terminals A, B, and SGND are generally used, with 485A and 485B terminals. Can achieve Modbus RTU communication or use PLC specific protocol communication. | |
LAN port | Connect network interface devices (PLC/touch screen, etc.) and support Modbus protocol or PLC dedicated protocol communication. | ||
power interface | Wide power input (DC 9-30V), built-in power reverse protection and overvoltage/overcurrent protection. | ||
SIM/UIM card interface | Drawer style SIM card holder, supporting 1.8V/3V SIM/UIM cards, with built-in 15KV ESD protection. | ||
Antenna interface (WIFI/4G) | Standard SMA female antenna interface with a characteristic impedance of 50 ohms. | ||
Reload button | Press for 1 second to enter the gateway local web configuration page. Press and hold for more than 10 seconds, and the gateway will be restored to the factory (note: at this time, the driver information and variables configured on the platform will also be cleared, make sure to use them properly) | ||
Summary of PLC protocol support | ||
brand | protocol support | Specific model (measured) |
Siemens | Serial port: PPI | protocol Network port: S7 protocol | S7-200,200SMART,1200,1500,300/400Network interface |
Mitsubishi | Serial port: programming port, Q/FX series MC protocol Network port: Q/FX series MC protocol | FX1S,FX1N,FX2N,FX3U/G,FX5U,Qseries |
Xinjie | Serial port: XC, XD protocol | XC,XD |
Yonghong | Serial port: Yonghong dedicated protocol | FBS |
DELTA | Serial port: DVP series protocol Network port: AS series protocol | DVP series, AS series |
Omron | Serial port: FINS protocol, extending HostLink Network port: FINS protocol | C,CV,CS/CJ/CP |
hollysys | Serial port: Helishi Modbus RTU | LE series PLC |
Inovance | Network port: AM600, H3U protocol Serial port: compatible with Mitsubishi programming port | Network: AM600, H3U Telephone: H1S (H0U H1U H1S H2U H2S) |
Rockwell (AB) | Network port: CIP, CIP-PCCC protocol | The cip pccc protocol only supports microLogix 1400 CIP protocol supports compactLogix series PLCs |
Modbus (instrument/touch screen) | Serial port: Modbus RTU protocol Network port: Modbus TCP protocol | Sensors, lower level machines supporting modbus protocol |
Electricity Agreement | Serial port: DLT645-2007 | |
Other agreements continue to be updated, please stay tuned | ||